Ground Fault Circuit Interrupter (GFCI) technology was first introduced in the NEC in 1971, yet four decades later the technology has not been introduced to a great extent outside of the home environment. This thesis introduces the difficulties encountered in low-voltage three phase ground fault current detection, and adopts a previously patented tripping scheme to develop and prototype a digital relay for 3-phase 480 volt systems capable of the sensitivity and speed required for personnel safety. Results demonstrate the feasibility of the concept and suggest commercial development should be pursued. The prototype is capable of mA sensitivity and reliably detects and removes the faulted feeder from the system, without causing false tripping on non-faulted feeders. The prototype system has been tested and responds appropriately for faults over the 1 mA to 1000 A range.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.