An axial flow fan design methodology is developed to design large diameter, low pressure rise, rotor-only fans for large air-cooled heat exchangers. The procedure aims to design highly efficient axial flow fans that perform well when subjected to off design conditions commonly encountered in air-cooled heat exchangers. The procedure makes use of several optimisation steps in order to achieve this. These steps include optimising the hub-tip ratio, vortex distribution, blading and aerofoil camber distributions in order to attain maximum total-to-static efficiency at the design point.
In order to validate the design procedure a 24 ft, 8 bladed axial flow fan is designed to the specifications required for an air-cooled heat exchanger for a concentrated solar power (CSP) plant. The designed fan is numerically evaluated using both a modified version of the actuator disk model and a three dimensional periodic fan blade model. The results of these CFD simulations are used to evaluate the design procedure by comparing the fan performance characteristic data to the design specification and values calculated by the design code. The flow field directly down stream of the fan is also analysed in order to evaluate how closely the numerically predicted flow field matches the designed flow field, as well as determine whether the assumptions made in the design procedure are reasonable.
The fan is found to meet the required pressure rise, however the fan total-to-static efficiency is found to be lower than estimated during the design process. The actuator disk model is found to under estimate the power consumption of the fan, however the actuator disk model does provide a reasonable estimate of the exit flow conditions as well as the total-to-static pressure characteristic of the fan.
An axial flow fan developed in the previous study is tested in order to characterize its performance. The M-fan, a 7.3152 m diameter rotor only axial flow fan was designed to perform well under the challenging operating conditions encountered in air-cooled heat exchangers. Preliminary computational fluid dynamics (CFD) results obtained using an actuator disk model (ADM) as well as a periodic three dimensional model indicate that the fan meets the specified performance targets, with an expected total-to-static efficiency of 59.4% and a total-to-static pressure rise of 114.7 Pa at the operating point. Experimental tests are performed on the M-fan in order to determine its performance across a full range of flow rates. A range of fan configurations are tested in order to ascertain the effect of tip clearance, blade angle, and hub configuration on fan performance. Due to the lack of a suitable facility for testing a large diameter fan, a scaled 1.542 m diameter model is tested on the ISO 5801 type A fan test facility at Stellenbosch University. A Reynolds-averaged Navier–Stokes CFD model representing the M-fan in the test facility is also developed in order to provide additional insight into the flow field in the vicinity of the fan blades. The results of the CFD model will be validated using the experimental data obtained. Both the CFD results and the experimental data obtained are compared to the initial CFD results for the full scale fan, as obtained in the previous study, by means of fan scaling laws. Experimental data indicate that the M-fan does not meet the pressure requirement set out in the initial study at the design blade setting angle of 34 deg. Under these conditions, the M-fan attains a total-to-static pressure rise of 102.5 Pa and a total-to-static efficiency of 56.4%, running with a tip gap of 2 mm. Increasing the blade angle is shown to be a potential remedy, improving the total-to-static pressure rise and efficiency obtained at the operating point. The M-fan is also shown to be highly sensitive to increasing tip gap, with larger tip gaps substantially reducing fan performance. The losses due to tip gap are also shown to be overestimated by the CFD simulations. Both experimental and numerically obtained results indicate lower fan total-to-static efficiencies than obtained in the initial CFD study. Results indicate that the M-fan is suited to its intended application, however, it should be operated with a smaller tip gap than initially recommended and a larger blade setting angle. Hub configuration is also shown to have an influence on fan performance, potentially improving performance at low flow rates.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.