The paper identifies a severe form of Low Order Harmonic Resonance problem in an HVdcfac system. It then seeks solutions to the problem by HVdc control means. This is achieved by a proper design of the Voltage Dependent Current Order Limiter (VDCOL), the Current Regulator and Timing Pulse generator. Supplementary control loops have also been introduced to result in a satisfactory performance as compared to that obtained with the use of uncharacteristic harmonic filter on the ac side. Robustness of a11 the options has been demonstrated through recovery performance of the dc link in response to 3-phase 5 cycle faults on both rectifier and inverter commutating buses.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.