HVAC control strategies that exploit temporal variations in zone occupancy have been well studied. Occupancy can also vary spatially within a zone, especially during off-design operating conditions. We complement prior work by studying the usefulness of sensing occupancy information at different spatial resolutions in large zones served by multiple AHUs. As conventional PID controllers cannot utilize this information effectively, we propose a new control strategy and study the usefulness of sensing. We observe that utility of sensing occupancy at finer spatial resolutions is higher when the actual spatial heterogeneity in occupancy is higher.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.