This paper evaluates the effect of a lightning strike directly on the 24 kV distribution lines in Thailand, where such strikes are one of the main causes of power outages. The voltage across the insulator, and the arrester energy absorbed due to the lightning, need to be analyzed for different grounding distances of the overhead ground wire, ground resistance, lightning impact positions, and lightning current waveforms. Analysis and simulations are conducted using the Alternative Transients Program/Electromagnetic Transients Program (ATP/EMTP) to find the energy absorbed by the arrester and the voltages across the insulator. The results indicate that when surge arresters are not installed, the voltage across the insulator at the end of the line is approximately 1.4 times that in the middle of the line. In addition, the ground resistance and grounding distance of the overhead ground wire affect the voltage across the insulator if the overhead ground wire is struck. When surge arresters are installed, a shorter grounding distance of the overhead ground wire and a lower ground resistance are not always desirable; this is because they reduce the back-flashover rate and the voltage across the insulator if lightning strikes the overhead ground wire. However, lightning strikes to the phase conductor result in high arrester energy and the possibility that the arrester will fail. Furthermore, the tail time of the lightning waveform is a significant variable when considering the energy absorbed by the arrester, whereas the front time is important for the voltage across the insulator. In case lightning strikes directly on the connected point between the overhead lines and the underground cables, the distribution line system is protected only by the lightning arrester at the connection point. The overvoltage at the connection point is lower than the basic impulse level at 24 kV of 125 kV, but the overvoltage at the end of the cable is still more than 125 kV in case the cable is longer than 400 m. When the distribution line system is protected by the lightning arrester at both the connection point and the end of the cable, it results in overvoltage throughout the cable is lower than the critical flashover of insulation. This method is the best way to reduce the failure rate of underground cables and equipment that are connected to the distribution line system.
This study determines the voltage across insulators after a direct lightning strike to an overhead ground wire on a 24 kV pole structure for different grounding distances of overhead ground wire, to calculate the maximum ground resistance required to avoid disruption of the distribution line system using ATP-EMTP software. The results show that when a 40 kA lightning current, the average lightning current in Thailand, strikes a 24 kV pole structure, the maximum ground resistance should not exceed 4 Ω for a 40 m grounding distance of overhead ground wire, based on an existing critical insulator flashover of 205 kV. However, because the average ground resistance in Thailand is approximately 10 Ω, this study proposes increasing the insulation level from 205 kV to 300 kV to reduce the likelihood of power outage. The cost-effectiveness of such an investment is assessed in terms of net present value (NPV), internal rate of return (IRR), profitability index (PI), and discounted payback period (DPP) using existing economic tools. Results show that when the critical insulator flashover is increased from 205 kV to 300 kV for a 40 m grounding distance of overhead ground wire, the project is likely to have a DPP of 15.12 years, NPV of 143,321.87 USD, IRR of 12%, and PI of 1.15. On the other hand, grounding distances greater than 40 m for overhead ground wire result in negative NPV, although the back flashover rate can be reduced by 1.51–5.71% with grounding distances of 80–200 m compared to the situation in the absence of grounding.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.