1Abstract-Harmonic current sharing is an important aspect of islanded microgrid due to the presence of nonlinear loads. The existing harmonic current sharing strategies suggest a trade-off between voltage quality and harmonic sharing effectiveness. In this paper, a novel control strategy is proposed to achieve current harmonic sharing by directly controlling the inherent impedance of the inverter. The proposed technique achieves harmonic sharing, in a distributed generation (DG) based islanded microgrid, without using any communication infrastructure. This paper also proposes a droop technique to distribute the harmonics generated by the nonlinear load as per the kVA ratings of different DG units in the system. The proposed concept of variable inverter impedance and its application in an islanded microgrid is validated using experimental studies.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.