Abstract-This paper presents a genetic algorithm to seek the optimal location of multi-type FACTS devices in a power system. The optimizations are performed on three parameters: the location of the devices, their types and their values. The system loadability is applied as measure of power system performance. Four different kinds of FACTS controllers are used and modeled for steady-state studies: TCSC, TCPST, TCVR and SVC. Simulations are done on a 118-bus power system for several numbers of devices. Results show the difference of efficiency of the devices used in this context. They also show that the simultaneous use of several kinds of controllers is the most efficient solution to increase the loadability of the system. In all the cases (single-and multi-type FACTS devices), we observe a maximum number of devices beyond which this loadability cannot be improved.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.