Abstruct-This paper explores the impact of six-phase transmission line faults and their subsequent fault clearing and reclosing on the torsional torques induced in turbine-generator shafts. In this context, investigations have been conducted on a large turbine-generator unit connected to a sample power system. The paper presents also a comparison between the torsional stresses induced in the turbine-generator shafts during these events with their corresponding disturbances of a threephase transmission system The results of these investigations are presented in the form of typical time responses as well as parametric studies. The EMTP is used for the simulation studies.The studies conclude that six-phase transmission line faults generally induce torsional torques in the turbine-generator shaft whose magnitudes are relatively higher than those induced due to transmission line faults in a three-phase system. This conclusion is true for both sustained faults and faults followed by clearing and high-speed reclosing operations.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.