This paper presents a current control technique for a three-phase grid-connected DC /AC inverter which is used in photovoltaic systems. A Proportional-Resonant (PR) controller is used for replacing the conventional Proportional-Integral (PI) controller in this system. By comparison with the conventional PI control method, the PR control can introduce an infinite gain at the fundamental frequency and hence can achieve zero steady-state error. The proposed model is based on two control loops: the first control loop regulates DC link voltage and the second one is used to keep the injected current to the grid in phase with the voltage by means of a Phase Locked Loop (PLL) in order to achieve a unit power factor and to adjust the output power as required. In order to examine the effectiveness of the suggested control, a simulation using the Matlab/Simulink software has been done and it’s concluded from the simulation results that the presented control by using the PR controller can be able to maintain maximum active power and to keep always a unity power factor despite variation load.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.