A differential pressure transmitter with an orifice is widely used as a major field flowmeter. A major drawback of this flowmeter at operation site is blockage of an impulse line, which connects a differential pressure transmitter with an orifice tap. By conducting experiments at a water line, we have developed a method to diagnose the blockage of the impulse line based on the evaluation of pressure fluctuations; this is installed on a multi-sensing differential pressure transmitter. This paper utilizes this method to diagnose the blockage at an oil line that carries a highly viscous fluid. In particular, we focus on the relation between the amplitude of the pressure fluctuations at the oil line and the kinetic viscosity (1.0 × 10 -5 to 3.0 × 10 -5 m 2 /s). Through experimental investigations, the following results are derived: (1) The highly viscous fluid in the impulse line does not attenuate the pressure fluctuations transmitting to the multi-sensing differential pressure transmitter. (2) Highly viscous flow in the main line has small pressure fluctuations; however, these fluctuations have the same characteristics of the impulse line blockage as those at a water line. Therefore, the proposed method can diagnose the impulse line blockage at an oil line as well as at a water line.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.