This paper investigates the effectiveness of two types of passive filters used for harmonic mitigation in a power system containing multiple capacitors and harmonic sources that cause multiple resonance points. They are notch and second order types installed at the point of common coupling (PCC) and include the utility capacitor bank as a component in their designs. Traditionally, the focus is only on mitigating total harmonic distortions (THDv & THDi). In this study their effectiveness is extended to evaluate the impact of these filters in terms of Total Power, Efficiency and Severity of Resonance factors when an unacceptable distortion is present. The effectiveness is investigated using the SUPERHARM/TOP software package. Computer models are developed to conduct harmonic penetration and harmonic scan resonance studies. Case studies are conducted for a network without a filter, with a notch filter and then with a second order filter. The filters are analysed at the input to the network and effectiveness factors are used to evaluate efficiency.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.