Datacenters spend $10-25 per watt in provisioning their power infrastructure, regardless of the watts actually consumed. Since peak power needs arise rarely, provisioning power infrastructure for them can be expensive. One can, thus, aggressively under-provision infrastructure assuming that simultaneous peak draw across all equipment will happen rarely. The resulting non-zero probability of emergency events where power needs exceed provisioned capacity, however small, mandates graceful reaction mechanisms to cap the power draw instead of leaving it to disruptive circuit breakers/fuses. Existing strategies for power capping use temporal knobs local to a server that throttle the rate of execution (using power modes), and/or spatial knobs that redirect/migrate excess load to regions of the datacenter with more power headroom. We show these mechanisms to have performance degrading ramifications, and propose an entirely orthogonal solution that leverages existing UPS batteries to temporarily augment the utility supply during emergencies. We build an experimental prototype to demonstrate such power capping on a cluster of 8 servers, each with an individual battery, and implement several online heuristics in the context of different datacenter workloads to evaluate their effectiveness in handling power emergencies. We show that: (i) our battery-based solution can handle emergencies of short duration on its own, (ii) supplement existing reaction mechanisms to enhance their efficacy for longer emergencies, and (iii) battery even provide feasible options when other knobs do not suffice.
Energy storage -in the form of UPS units -in a datacenter has been primarily used to fail-over to diesel generators upon power outages. There has been recent interest in using these Energy Storage Devices (ESDs) for demand-response (DR) to either shift peak demand away from high tariff periods, or to shave demand allowing aggressive under-provisioning of the power infrastructure. All such prior work has only considered a single/specific type of ESD (typically re-chargeable lead-acid batteries), and has only employed them at a single level of the power delivery network. Continuing technological advances have provided us a plethora of competitive ESD options ranging from ultra-capacitors, to different kinds of batteries, flywheels and even compressed air-based storage. These ESDs offer very different trade-offs between their power and energy costs, densities, lifetimes, and energy efficiency, among other factors, suggesting that employing hybrid combinations of these may allow more effective DR than with a single technology. Furthermore, ESDs can be placed at different, and possibly multiple, levels of the power delivery hierarchy with different associated trade-offs. To our knowledge, no prior work has studied the extensive design space involving multiple ESD technology provisioning and placement options. This paper intends to fill this critical void, by presenting a theoretical framework for capturing important characteristics of different ESD technologies, the trade-offs of placing them at different levels of the power hierarchy, and quantifying the resulting cost-benefit trade-offs as a function of workload properties.
Power infrastructure contributes to a significant portion of datacenter expenditures. Overbooking this infrastructure for a high percentile of the needs is becoming more attractive than for occasional peaks. There exist several computing knobs to cap the power draw within such under-provisioned capacity. Recently, batteries and other energy storage devices have been proposed to provide a complementary alternative to these knobs, which when decentralized (or hierarchically placed), can temporarily take the load to suppress power peaks propagating up the hierarchy. With aggressive under-provisioning, the power hierarchy becomes as central a datacenter resource as other computing resources, making it imperative to carefully allocate, isolate and manage this resource (including batteries), across applications. Towards this goal, we present vPower , a software system to virtualize power distribution. vPower includes mechanisms and policies to provide a virtual power hierarchy for each application. It leverages traditional computing knobs as well as batteries, to apportion and manage the infrastructure between co-existing applications in the hierarchy. vPower allows applications to specify their power needs, performs admission control and placement, dynamically monitors power usage, and enforces allocations for fairness and system efficiency. Using several datacenter applications, and a 2-level power hierarchy prototype containing batteries at both levels, we demonstrate the effectiveness of vPower when working in an under-provisioned power infrastructure, using the right computing knobs and the right batteries at the right time. Results show over 50% improved system utilization and scale-out for vPower's over-booking, and between 12-28% better application performance than traditional power-capping control knobs. It also ensures isolation between applications competing for power.
Despite the growing popularity of Solid State Disks (SSDs) in the datacenter, little is known about their reliability characteristics in the field. The little knowledge is mainly vendor supplied, which cannot really help understand how SSD failures can manifest and impact production systems, in order to take appropriate actions. Besides failure data, a detailed characterization requires wide spectrum of data about factors influencing SSD failures, right from provisioning (what models' where and when deployed' etc.) to the operational ones (workloads, read-write intensities, write amplification, etc.). We analyze over half a million SSDs that span multiple generations spread across several datacenters which host a wide range of workloads over nearly 3 years. By studying the diverse set of factors on SSD failures, and their symptoms, our work provides the first look at the what, when and why characteristics of SSD failures in production datacenters.
Datacenters spend $10-25 per watt in provisioning their power infrastructure, regardless of the watts actually consumed. Since peak power needs arise rarely, provisioning power infrastructure for them can be expensive. One can, thus, aggressively under-provision infrastructure assuming that simultaneous peak draw across all equipment will happen rarely. The resulting non-zero probability of emergency events where power needs exceed provisioned capacity, however small, mandates graceful reaction mechanisms to cap the power draw instead of leaving it to disruptive circuit breakers/fuses. Existing strategies for power capping use temporal knobs local to a server that throttle the rate of execution (using power modes), and/or spatial knobs that redirect/migrate excess load to regions of the datacenter with more power headroom. We show these mechanisms to have performance degrading ramifications, and propose an entirely orthogonal solution that leverages existing UPS batteries to temporarily augment the utility supply during emergencies. We build an experimental prototype to demonstrate such power capping on a cluster of 8 servers, each with an individual battery, and implement several online heuristics in the context of different datacenter workloads to evaluate their effectiveness in handling power emergencies. We show that: (i) our battery-based solution can handle emergencies of short duration on its own, (ii) supplement existing reaction mechanisms to enhance their efficacy for longer emergencies, and (iii) battery even provide feasible options when other knobs do not suffice.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.
customersupport@researchsolutions.com
10624 S. Eastern Ave., Ste. A-614
Henderson, NV 89052, USA
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
Copyright © 2025 scite LLC. All rights reserved.
Made with 💙 for researchers
Part of the Research Solutions Family.