Low delta-T syndrome often occurs in building chilled water systems, which makes systems fail to operate as efficiently as originally anticipated. Extensive studies have been conducted on the subject of low delta-T syndrome with the aims of investigating the potential causes behind and the ways to keep delta-T high. This paper addresses to explain the causes of degrading delta-T from a mathematic perspective and to analyze the impacts of important operational parameters on the delta-T quantitatively. A simplified global cooling coil model representing the relationship between the total cooling load and the total water flow rate of chilled water systems is developed, which can be used to predict the system delta-T under different load distribution and system operation conditions. It is proved mathematically that the load distribution characteristic is an important factor in influencing the system delta-T of a chilled water system. This finding explains why the system delta-T is always lower than the delta-T of individual coils, particularly under low partial load conditions. A system-level fault detection and diagnosis (FDD) method is proposed for identifying the possible causes of the low delta-T problem. A case study is conducted to validate the proposed global model and FDD method in a real building.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.