The AISC 2002 Seismic Provisions for Structural Steel Buildings recommend that usage and sizing of beam flange continuity plates across the column web shall be based on tests. The Recommended Seismic Design Criteria for New Steel Moment-Frame Buildings ( FEMA-350) state that unless project-specific testing is performed to demonstrate that continuity plates are not required, moment-resisting connections should be provided with continuity plates when the thickness of the column flange is below a minimum value. One of the preferred moment connections for seismic-resistant steel frames is the reduced beam section (RBS) moment connection, which has performed well under cyclic loads in laboratory testing. To demonstrate the effectiveness of the RBS moment connection without continuity plates in the panel zone, a series of four full-scale tests of exterior beam-column connections was carried out. All materials were A572 Grade 50 steel; the beams were W30×132, two of the assemblies used W14×283 columns, and the other two used W18×211 columns. The beams were welded to the columns using complete joint-penetration welds. All four tests demonstrated that the RBS connections without continuity plates developed a total interstory drift angle greater than 0.04 radians and met the requirements for special moment frames.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.