The existing methods for estimating harmonic impedance usually assume that harmonic impedance is constant in a measurement period. However, for a variety of practical reasons, such as the load change of power grid, utility harmonic impedance may be changed. So a reasonable hypothesis is that utility harmonic impedance is time-varying, but the variation of the impedance is not large at adjacent sampling time. Thus, this paper proposes a novel method to estimate utility harmonic impedance by taking the criterion of minimum norm of impedance differences at adjacent sampling times with a measurement period. According to the proposed criterion, an objective function is built with the norm of the harmonic impedance differences and utility harmonic voltage differences of adjacent moments. And then, the utility harmonic impedance can be obtained by minimizing the objective function. The proposed method has high accuracy even while background harmonic emission level is high and harmonic impedance of customer side is not much larger than that of utility side. The effectiveness is verified by the simulation and field cases. In the simulation, the estimation errors of most cases are within 10% and the maximum error is not exceed 16%.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.