3D heating hazard assessment on transformer covers. Arrangement decisions

Abstract: Purpose -The purpose of this paper is to apply a 3D methodology to assess the heating hazard on transformer covers and present a practical tool to design amagnetic inserts arrangement. Design/methodology/approach -A practical 3D methodology linking an electromagnetic analytical formulation with thermal finite element method is used for computation. Such methodology allows the evaluation of the temperature on metallic device elements heated by electromagnetic induction. This is a 3D problem which in the case of… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
3
1

Citation Types

0
4
0

Year Published

2012
2012
2016
2016

Publication Types

Select...
3
3

Relationship

1
5

Authors

Journals

citations
Cited by 12 publications
(4 citation statements)
references
References 11 publications
0
4
0
Order By: Relevance
“…Figure 6(b) shows the temperature distribution if the flat cover base is made from mild steel and the bushing turrets are instead made from a magnetic material. Stainless steel material properties might be determined from experiments (Penabad-Duran et al, 2012) applying the parameter identification technique presented in this paper. It can be seen how due to the proper combination of materials, the temperature is reduced to permitted values.…”
Section: Practical Application: Overheating Evaluation On 3d Complex mentioning
confidence: 99%
See 1 more Smart Citation
“…Figure 6(b) shows the temperature distribution if the flat cover base is made from mild steel and the bushing turrets are instead made from a magnetic material. Stainless steel material properties might be determined from experiments (Penabad-Duran et al, 2012) applying the parameter identification technique presented in this paper. It can be seen how due to the proper combination of materials, the temperature is reduced to permitted values.…”
Section: Practical Application: Overheating Evaluation On 3d Complex mentioning
confidence: 99%
“…Most of the related works focus their results on loss prediction (Kulkarni et al, 2004;Milagre et al, 2012) to ensure their total values, however the thermal problem for hot spot localization has become more significant in recent years (Cranganu-Cretu and Schneider, 2009;Glotic et al, 2009). It allows the effective design of the structural transformer elements guaranteeing total losses, maximum permitted temperature rise and considering also material cost (Penabad-Duran et al, 2012;Di Barba et al, 2005) which has acquired importance among designers and manufacturers imposed by the severe competitive market situation.…”
Section: Introductionmentioning
confidence: 99%
“…These cables are connected to bushings mounted in the tank walls or cover. High currents produce high stray fields in the vicinity of the bushing holes and this can produce high stray losses and hot spots in these parts of the tank [1]- [5]. In this paper authors analyze the case of tertiary voltage bushings placed in the tank cover.…”
Section: Introductionmentioning
confidence: 99%
“…This is because a very fine mesh is required in the thin skin depth of leakage flux penetration of about one millimeter against the dimensions of a few meters of the volume of the device (Lopez-Fernandez et al , 2012a, b, c). Nevertheless, analytical methods are being used as they still offer advantages in terms of fast calculation, in certain applications, when the non-linearity of magnetic characteristics is properly incorporated into the formulation (Penabad-Duran et al , 2012; Lopez-Fernandez et al , 2012a, b, c). The assessment of stray losses was an early concern, where, the classical solution was to adopt a losses correction factor.…”
Section: Introductionmentioning
confidence: 99%