2020
DOI: 10.7731/kifse.2020.34.1.055
|View full text |Cite
|
Sign up to set email alerts
|

A Study on Fire Spread and Evacuation Risk of Conduit Combustion in Ceiling Hiding Place

Abstract: In this study, the ISO 5660 and ISO 5659 combustion tests were conducted with synthetic resin conduits (CD, VE) and metal conduit (ST) used for wiring work in electrical facilities, which can be installed in ceiling concealed places. Then, fire spreading and evacuation risks were analyzed based on the measured data. In the ISO 5660 test, CD of 120.5 MJ/㎡, VE of 81.9 MJ/㎡, and ST of 4.9 MJ/㎡ were measured. In the ISO 5659 test, the CD 1320, VE 731, and ST 102 were measured, and then the maximum smoke densities … Show more