Advancing new techniques for UHF PDdetection and localization in the power transformers in the factory tests

Abstract: Partial discharge (PD) detection in the ultra-high frequency (UHF) range is state of the art. One of the most critical points in this detection method is adopting proper and suitable antenna design. In this paper, a new design of UHF antennas is introduced which is suitable to be used on the transformers in the HV laboratories of the manufacturers. To ensure the applicability of the new antenna, experimental UHF PD measurements are carried out on a transformer tank model as well as on the real power transforme… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1

Citation Types

0
43
0

Year Published

2016
2016
2024
2024

Publication Types

Select...
7
2

Relationship

0
9

Authors

Journals

citations
Cited by 93 publications
(43 citation statements)
references
References 15 publications
0
43
0
Order By: Relevance
“…Additionally, all four sensors should not be placed on the same tank wall, and two sensors on the same tank wall should not be placed close together. Lastly, all four sensors should not form a geometrical plane [27]. However, using additional sensors can aid in PD source localization in case four sensors cannot provide enough information in the TDOA.…”
Section: Proposals For Optimal Sensor Placement For Pd Source Localizmentioning
confidence: 99%
“…Additionally, all four sensors should not be placed on the same tank wall, and two sensors on the same tank wall should not be placed close together. Lastly, all four sensors should not form a geometrical plane [27]. However, using additional sensors can aid in PD source localization in case four sensors cannot provide enough information in the TDOA.…”
Section: Proposals For Optimal Sensor Placement For Pd Source Localizmentioning
confidence: 99%
“…Neutral current defined in (5) for no-load condition and in (13) for load condition will never be zero due to different types of imbalances. Imbalance in supply voltages i.e.…”
Section: A Relation Of Transformer Winding Parameters and Intakementioning
confidence: 99%
“… 13. Experimental results for interturn fault at defined load condition primary side intake currents waveforms and corrected phasor diagrams with the neutral current when fault on (a) Primary winding with phase-a and (b) Secondary winding with phase-b.…”
mentioning
confidence: 99%
“…Therefore, the detection of PD signal is an effective way for Condition Monitoring and Diagnostics (CMD) in substation. Among the PD detection methods, ultra-high frequency (UHF) electromagnetic waves is the most effective method due to its excellent sensitivity and propagation speed [3]. For the existing UHF PD measurement techniques, due to limited hardware conditions such as analog to digital conversion, it is often difficult to meet the requirement of high sampling rate.…”
Section: Introductionmentioning
confidence: 99%