“…However, in simulation, the autotransformer is considered to have a finite value of leakage reactance, leading to commutation overlap. In comparison with the total magnetics ratings of conventional Δ/Y/Δ 12-pulse isolated transformer (109.6%) [6], T-connected 24-pulse autotransformer (39.9%) [7], fork-connected 18-pulse autotransformer (39.7%) [9], star-connected 24-pulse autotransformer (91.0%) [13], asymmetrical polygon 20-pulse autotransformer (45.5%) [17], and T-connected 36-pulse autotransformer (61.9%) [22] based AC-DC converters, the total ratings of magnetics of the proposed 36-pulse rectifier scheme is much less. The detailed comparison results are tabulated in Table 5.…”