-A steel modular unit structural system has been used increasingly for mid and high-rise buildings, since the building can be easily constructed by assembling the pre-made modular unit structures. For this structural system, each modular unit structures have to be properly connected to the foundation to transfer the axial force and the bending moment that are generated from external load to the ground. In this study, a new type of the embedded steel column-to-foundation connection was proposed, and its flexural behavior was evaluated through a series of experimental study. Five full scale specimens for the proposed connections were constructed and tested. The effect of the main parameters that affect the flexural behavior of the proposed connection, such as embedment length and shape of end plate, were studied. From the results, it was found that the flexural stiffness of the proposed connection was higher than that of the semi-rigid connection for all test specimens, and 200 mm of embedment length was proper for the given test specimens in this study. , 하태휴 (2013) 등은 내력벽식 스터드패널을 이용 한 모듈러 유닛의 내진성능 평가 연구를 수행한바 있다 [6] . 이 상섭 (2013) 등은 유닛 내의 최적의 상세 개선을 위한 기둥-보 조인트에 대한 실험적 연구를 수행하였다 [7] .