2015
DOI: 10.1109/mei.2015.7214442
|View full text |Cite
|
Sign up to set email alerts
|

Determining water in transformer paper insulation: analyzing aging transformers

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
4
1

Citation Types

0
9
0
1

Year Published

2017
2017
2024
2024

Publication Types

Select...
5
3
1

Relationship

0
9

Authors

Journals

citations
Cited by 38 publications
(10 citation statements)
references
References 17 publications
0
9
0
1
Order By: Relevance
“…Moisture partition between oil and paper is assumed to reach an equilibrium, but practically this assumption will not be achieved because of varying transformer temperature. Martin et al [30, 31] have investigated moisture migrations in oil–paper insulation system and inferred that moisture is present in oil at higher temperatures and migrates into paper at lower temperatures. These migrations of moisture within oil–paper insulation form an aqueous solution with oil.…”
Section: Resultsmentioning
confidence: 99%
“…Moisture partition between oil and paper is assumed to reach an equilibrium, but practically this assumption will not be achieved because of varying transformer temperature. Martin et al [30, 31] have investigated moisture migrations in oil–paper insulation system and inferred that moisture is present in oil at higher temperatures and migrates into paper at lower temperatures. These migrations of moisture within oil–paper insulation form an aqueous solution with oil.…”
Section: Resultsmentioning
confidence: 99%
“…The degree of polymerization (DP) and tensile strength (TS) of paper are reduced and these precipitate the deterioration of the solid insulation. The aging mechanism also leads to the formation of dissolved gases in oil, hence degrading the physico-chemical properties of the insulation system [6,18,19]. Consequently, assessing and monitoring the oil/paper insulation is crucial in order to maintain a reliable operation of power transformers.…”
Section: Introductionmentioning
confidence: 99%
“…aging [4], [5]. The equipment may fail ultimately due to premature breakdown when insulation reaches the end of its working life sooner as the insulation ages faster accompanied by water [4], [6]. Dampness has become the top threat among all the hazardous factors for insulation health.…”
Section: Introductionmentioning
confidence: 99%
“…Various techniques have been proposed to determine MCP for utilities to implement routine tests or laboratory studies. The most direct method is Karl Fischer titration (KFT) [6], [8]. Karl Fischer titration is a method in analytical chemistry that traces amounts of water in a sample using volumetric or coulometric titration.…”
Section: Introductionmentioning
confidence: 99%