2015 International Conference on Quality in Research (QiR) 2015
DOI: 10.1109/qir.2015.7374905
|View full text |Cite
|
Sign up to set email alerts
|

Frequency response measurement of a power transformer

Abstract: This paper presents a field experience in condition monitoring of a power transformer using SFRA technique. A design based comparison approach of the SFRA test results is discussed in the paper. In order to verify the latest condition of the transformer, the SFRA test was complemented with DGA and PD tests. The SFRA test results indicated that there is an abnormality within the transformer windings. The PD test results confirmed this interpretation, where very large ultrasonic impulses were detected. A series … Show more