Abstract: For high voltage impulse testing, a standard lightning impulse is defined in IEEE Std. 4 and IEC 60060-1 as a double exponential waveform having a front time T1 = 1.2 μs ± 30% and time to half-value T2 = 50 μs ± 20%. It has been noticed that for a given specimen, it is possible to successfully pass a flashover test at one end of the T1 tolerance range while failing the same test at the opposite end of the tolerance spectrum. Consequently, a systematic approach was adopted to investigate this observation. Up-an… Show more