“…5 (a) Probe constant as function of Re (b) standard design of the probe[88].. Bi-directional probe dimensions used in the current study (D=24.6 mm, L=46.25 mm, D'=6.3 mm, and L'=7.6 mm) Model Vertical temperature profiles from a 10 MW fire in the tunnel under different fan speeds (Note: -1.25 and 1.25 refer 1.25 m left and 1.25 m right from the centre, respectively)[79] Vertical profiles of oxygen mass fraction of the flow from a 10 MW fire in the tunnel under different fan speeds (Note: -1.25 and 1.25 refer 1.25 m left and 1.25 m right from the centre, respectively)[79] 10 Vertical velocity profiles at 50% fan speed without and with a 2.5 MW fire in the tunnel (Note: -1.25 and 1.25 refer 1.25 m left and 1.25 m right from the centre, respectively)[79] 11 Vertical velocity profiles at 50% fan speed from a atrium simulation and manual measurements (Note: -1 25. and 1.25 refer 1.25 m left and 1.25 m right from the centre, respectively) [79] 12 the fire most accurate velocity probe combinations [79] 13 Comparison of the fire most accurate velocity probe combinations [79] 16 Real-time HRR calculations and display system flow chart Test arrangement for Heptane and propane fire The front panel of the real time HRR measurement calculation and display system (captured during a test, 5 MW 50% fan speed) HRR results from a calibration test A5 of the HRR measurement system using propane burners (50% fan speed, 5 MW) The correction factor matching JQ to E from a calibration test A5 (50% fan speed, 5 MW) Comparisons of the system response to 5 MW calibration fire for different fan speeds Results from a calibration test P13 of the HRR measurement system using propane burners (100% fan speed, 13 MW, for 40 seconds) Results from a calibration test of the HRR measurement system using propane burners and heptane pool fire (100% fan speed, 23 MW) Correction factors with respect to 02 concentration Corrected HRR calculation for Test Bl 1 (25%, 8-2 MW Type B propane test, correction factor = 0.83) Uncertainty contributions by each component (averaged results from 11 tests) Performance of the HRR measurement system Test set-up in the tunnel 125 Flow straightening vanes at the main opening 125 Sprinkler system and instrumentation in the tunnel 129 The propane burners and heptane pool for the fire test of 15 MW 131 Plate thermometer (the manufacture provided) 133 Arrangement of buckets 134 Bucket test 135 The collected water spray rate normalised to the nominal water spray rate of3 1/min/m 2 under an air flow of 0 m/s 137 The collected water spray rate normalised to the nominal water spray rate of 3 1/min/m 2 under an air flow of 2.7 m/s (Fan speed 100%) 137 10 The collected water spray rate normalised to the nominal water spray rate of 9 1/min/m 2 under an air flow of 0 m/s 138 11 The collected water spray rate normalised to the nominal water spray rate of 9 1/min/m 2 under an air flow of 2.7 m/s (Fan speed 100%) 138 12 A photo taken during the suppression test 139 13 The measured HRR and O2 concentration over time for 10 MW fire with a 9 9…”