The use of a novel 3-port condensing wave rotor is suggested to enhance the turbocompression in a refrigeration cycle that works only with water (R718) as a refrigerant. Although the implementation of such a wave rotor essentially reduces the size and cost of R718 units, their efficiency may also be increased. The condensing wave rotor employs pressurized water to pressurize, desuperheat, and condense the refrigerant vapor, all in one dynamic process. The underlying phenomena of flash evaporation, shock wave compression, desuperheating, and condensation inside the wave rotor channels are described in a wave and phase-change diagram. The thermodynamic process is shown in pressure-enthalpy and temperature-entropy diagrams. Based on the described thermodynamic model, a computer program was generated to evaluate the performance of R718 baseline and wave-rotor-enhanced cycles. The effect of some key parameters on the performance enhancement is demonstrated as an aid for optimization. A performance map summarizes the findings. It shows optimum wave rotor pressure ratio and maximum relative performance improvement of R718 cycles by using the 3-port condensing wave rotor.
Using a novel 3-port condensing wave rotor enhancing the turbocompression in a R718 refrigeration cycle, which uses only water as a refrigerant, has been introduced. The wave-rotor implementation can increase efficiency and reduce size and cost of R718 units. The condensing wave rotor employs pressurized water to pressurize, desuperheat, and condense the refrigerant vapor—all in one dynamic process. The underlying phenomena of flash evaporation, shock wave compression, desuperheating, and condensation inside the wave rotor channels are described in a wave and phase-change diagram. The thermodynamic process is shown in pressure–enthalpy and temperature–entropy diagrams. A computer program based on a thermodynamic model was generated to evaluate the performance of R718 baseline and wave-rotor-enhanced cycles. The effect of some key parameters on the performance enhancement is demonstrated as an aid for optimization. A performance map summarizes the findings. It shows optimum wave rotor pressure ratio and maximum relative performance improvement of R718 cycles by using the 3-port condensing wave rotor.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.