The present work deals with the heat transfer performance of a copper-water loop heat pipe (LHP) with a flat oval evaporator in steady-state operation. Modeling the heat transfer in the evaporator was particularly studied, and the evaporation heat transfer coefficient was determined from a dimensionless correlation developed based on experimental data from the literature. The model was based on steady-state energy balance equations for each LHP component. The model results were compared to the experimental ones for various heat loads, cooling temperatures, and elevations, and a good agreement was obtained. Finally, a parametric study was conducted to show the effects of different key parameters, such as the axial conductive heat leaks between the evaporator and the compensation chamber cases, the capillary structure porosity and material, and the groove dimensions.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.