In this paper the synchronous generator excitation control is designed using the model reference control approach and its predictive extension. The control objective is to satisfy requirements on the synchronous generator performances imposed by the transmission system operator. The structure of both controllers is expressed in the form of modified Laguerre network. The efficiency of the proposed control design procedure is illustrated by simulation of the 259 MVA synchronous generator of the nuclear power plant Mochovce in Slovakia.K e y w o r d s: model reference control, predictive control, Laguerre model, synchronous generator
Abstract-The model reference control based on modifiedLaguerre network is an open-loop control structure; therefore it has to be modified to ensure the disturbance rejection. In the paper a new modification using the closed loop with integrator is proposed. This Laguerre-based model reference control algorithm is compared with the control structure augmented by internal model and its stability, robustness and performances are analyzed.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.