balance point back. These tests indicate quite effects on the 110 kv lines, it was noted that the parclearly that the relay errors on double line-to-ground allel line, which was on the same towers, caused a faults, as expressed in equations 3 and 4, are variable shift in the relay balance point of approximately 1/3. and in general unpredictable, thus justifying the These tests indicate that where parallel lines are on switching arrangement whereby tripping is pre-the same towers, compensation must be made for the vented on double line-to-ground faults. mutual effects, if accurate distance measurement is
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.