Distance relay design is equipped with out-of-step tripping scheme to ensure correct distance relay operation during power swing. The out-of-step condition is a consequence result from unstable power swing. It requires proper detection of power swing to initiate a tripping signal followed by separation of unstable part from the entire power system. The distinguishing process of unstable swing from stable swing poses a challenging task. This paper presents an intelligent approach to detect power swing based on S-Transform signal processing tool. The proposed scheme is based on the use of S-Transform feature of active power at the distance relay measurement point. It is demonstrated that the proposed scheme is able to detect and discriminate the unstable swing from stable swing occurring in the system. To ascertain validity of the proposed scheme, simulations were carried out with the IEEE 39 bus system and its performance has been compared with the wavelet transform–based power swing detection scheme.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.