A multi-channel Variable Frequency Transformer (VFT) has been commissioned in Linden, New Jersey to provide control of 300 MW into New York City. The first two VFT installations, at Hydro-Québec's Langlois substation and at AEP's Laredo substation, are single-channel applications, and the Linden VFT is the first multi-channel VFT, with three channels in parallel. The core technology of the VFT is a rotary transformer with three-phase windings on both rotor and stator. The power flow through the VFT is controlled with a motor and drive system which adjusts the rotational position of the rotor relative to the stator. Although the VFT can interconnect two asynchronous power grids, the Linden VFT is connected between synchronous systems that have existing ties. The VFT was the preferred technology chosen for the Linden application because of its ability to continuously control power flow, its low risk of grid interactions, and its relatively small physical footprint. This paper describes the VFT application at Linden and demonstrates its performance and seamless integration.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.