We have newly developed an 80MVA GCT STATCOM for the Kanzaki substation of the Kansai Electric Power Co., Inc. It has been started commercial operation in June, 2004. The main purpose of the STATCOM is to maintain voltage during single circuit connection of source to the substation resulting from an AC system fault in order not to break down load system of the substation. The developed STATCOM has three distinctive features: (1) a high-efficient, compact and AC filter-less system using multistage three-level GCT converter and customized PWM; (2) a coordinated voltage regulator with tap control of main transformers; and (3) a continuous operation from a single phase-ground fault through reclosing of the faulted circuit by limiter adjustments of the reactive current reference. This paper describes characteristics of the coordinated voltage and validity the continuous operation during AC system faults using data of commercial operations and the simulation results.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.