1987
DOI: 10.1016/0378-7796(87)90049-6
|View full text |Cite
|
Sign up to set email alerts
|

Prediction of the Temperatures in a Three-Core Distribution Cable and Splice with Load Changes

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
3
1
1

Citation Types

0
7
0

Year Published

1992
1992
2023
2023

Publication Types

Select...
5
1

Relationship

0
6

Authors

Journals

citations
Cited by 7 publications
(7 citation statements)
references
References 1 publication
0
7
0
Order By: Relevance
“…As seen in the literatures [16,17], the temperature inside joints was calculated cooler than that of cable. The reason given by those papers was that the ferrule diameter was considerably larger than that of the conductor (27.2 mm compared with 19.1 mm) without consideration of contact resistance.…”
Section: The Effect Of Contact Resistance In Connectorsmentioning
confidence: 54%
See 3 more Smart Citations
“…As seen in the literatures [16,17], the temperature inside joints was calculated cooler than that of cable. The reason given by those papers was that the ferrule diameter was considerably larger than that of the conductor (27.2 mm compared with 19.1 mm) without consideration of contact resistance.…”
Section: The Effect Of Contact Resistance In Connectorsmentioning
confidence: 54%
“…Thus, "G-factors" can not be used to calculate this part of thermal resistance. What's more, a very important assumption made in [16,17] was that the cable and joint outer surfaces are isothermal. Nevertheless, according to the FEM thermal analysis as illustrated in Figure 15, the temperature difference in outer surface of the joint can reach over 10 • C due to its triangular shape, which demonstrates the joint outer surface is not isothermal.…”
Section: The Accuracies Comparison Between the Proposed Methods And Otmentioning
confidence: 99%
See 2 more Smart Citations
“…In this approach, the differential equation governing the axial and radial heat flows in an infinitely long conductor is applied to three longitudinal sections along the cable length exposed to different external conditions. Also in 1986, the effect of axial heat conduction in electric cables was further i n v e s t i g a t e d b y Weedy, who developed steady-state and transient thermal models for the determination of the axial temperature in threecore cables of infinite length jointed with splices and buried in the ground [51], [52] ( Figure 8). The transient thermal model considers several longitudinal subsections in which the multicore cable and splice are simplified into equivalent single-core conductors using a geometric factor of the IEC Standard, Publication 287.…”
Section: Autogrounddesignmentioning
confidence: 99%