The paper deals with a recent measurement improvement introduced into the Italian power quality monitoring system, concerning voltage dips detection and their proper evaluation in the presence of voltage transformer VT saturation phenomena. Saturation effects, essentially on network operated with isolated neutral, can give origin to "false" voltage dips, which can affect the on-line voltage monitoring during a few specific events (i.e. single line-to-ground faults). The "false dip" problem, on the other hand, can be considered negligible in compensated neutral networks. A new criterion has been developed in cooperation with the Polytechnic of Turin, based on the detection of a second harmonic component in the measured voltages, which, once provided with the proper setting parameters, can succeed in identifying "false" dips. The criterion effectiveness has been evaluated on field. The major advantage of the filter implementation in the monitoring system is that, from now on, network operated with isolated neutral could be considered quite similar to those operated with neutral compensation from the point of view of voltage dip performance.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.