Transpower New Zealand Limited has measured DC currents in transformer neutrals in the New Zealand electrical network at multiple South Island locations. Near‐continuous archived DC current data exist since 2001, starting with 12 different substations and expanding from 2009 to include 17 substations. From 2001 to 2015 up to 58 individual transformers were simultaneously monitored. Primarily, the measurements were intended to monitor the impact of the high‐voltage DC system linking the North and South Islands when it is operating in “Earth return” mode. However, after correcting for Earth return operation, as described here, the New Zealand measurements provide an unusually long and spatially detailed set of geomagnetically induced current (GIC) measurements. We examine the peak GIC magnitudes observed from these observations during two large geomagnetic storms on 6 November 2001 and 2 October 2013. Currents of ~30–50 A are observed, depending on the measurement location. There are large spatial variations in the GIC observations over comparatively small distances, which likely depend upon network layout and ground conductivity. We then go on to examine the GIC in transformers throughout the South Island during more than 151 h of geomagnetic storm conditions. We compare the GIC to the various magnitude and rate of change components of the magnetic field. Our results show that there is a strong correlation between the magnitude of the GIC and the rate of change of the horizontal magnetic field (H′). This correlation is particularly clear for transformers that show large GIC current during magnetic storms.
Geomagnetically induced current (GIC) observations made in New Zealand over 14 years show induction effects associated with a rapidly varying horizontal magnetic field (dBH/dt) during geomagnetic storms. This study analyzes the GIC observations in order to estimate the impact of extreme storms as a hazard to the power system in New Zealand. Analysis is undertaken of GIC in transformer number six in Islington, Christchurch (ISL M6), which had the highest observed currents during the 6 November 2001 storm. Using previously published values of 3,000 nT/min as a representation of an extreme storm with 100 year return period, induced currents of ~455 A were estimated for Islington (with the 95% confidence interval range being ~155–605 A). For 200 year return periods using 5,000 nT/min, current estimates reach ~755 A (confidence interval range 155–910 A). GIC measurements from the much shorter data set collected at transformer number 4 in Halfway Bush, Dunedin, (HWB T4), found induced currents to be consistently a factor of 3 higher than at Islington, suggesting equivalent extreme storm effects of ~460–1,815 A (100 year return) and ~460–2,720 A (200 year return). An estimate was undertaken of likely failure levels for single‐phase transformers, such as HWB T4 when it failed during the 6 November 2001 geomagnetic storm, identifying that induced currents of ~100 A can put such transformer types at risk of damage. Detailed modeling of the New Zealand power system is therefore required to put this regional analysis into a global context.
During space weather events, geomagnetically induced currents (GICs) can be induced in high‐voltage transmission networks, damaging individual transformers within substations. A common approach to modeling a transmission network has been to assume that every substation can be represented by a single resistance to Earth. We have extended that model by building a transformer‐level network representation of New Zealand's South Island transmission network. We represent every transformer winding at each earthed substation in the network by its known direct current resistance. Using this network representation significantly changes the GIC hazard assessment, compared to assessments based on the earlier assumption. Further, we have calculated the GIC flowing through a single phase of every individual transformer winding in the network. These transformer‐level GIC calculations show variation in GICs between transformers within a substation due to transformer characteristics and connections. The transformer‐level GIC calculations alter the hazard assessment by up to an order of magnitude in some places. In most cases the calculated GIC variations match measured variations in GIC flowing through the same transformers. This comparison with an extensive set of observations demonstrates the importance of transformer‐level GIC calculations in models used for hazard assessment.
Several periods of geomagnetically induced currents (GICs) were detected in the Halfway Bush substation in Dunedin, South Island, New Zealand, as a result of intense geomagnetic storm activity during 6 to 9 September 2017. Unprecedented data coverage from a unique combination of instrumentation is analyzed, that is, measurements of GIC on the single‐phase bank transformer T4 located within the substation, nearby magnetic field perturbation measurements, very low frequency (VLF) wideband measurements detecting the presence of power system harmonics, and high‐voltage harmonic distortion measurements. Two solar wind shocks occurred within 25 hr, generating four distinct periods of GIC. Two of the GIC events were associated with the arrival of the shocks themselves. These generated large but short‐lived GIC effects that resulted in no observable harmonic generation. Nearby and more distant magnetometers showed good agreement in measuring these global‐scale magnetic field perturbations. However, two subsequent longer‐lasting GIC periods, up to 30 min in duration, generated harmonics detected by the VLF receiver systems, when GIC levels continuously exceeded 15 A in T4. Nearby and more distant magnetometers showed differences in their measurements of the magnetic field perturbations at these times, suggesting the influence of small‐scale ionospheric current structures close to Dunedin. VLF receiver systems picked up harmonics from the substation, up to the 30th harmonic, consistent with observed high‐voltage increases in even harmonic distortion, along with small decreases in odd harmonic distortion.
Large geomagnetic storms are a known space weather hazard to power transmission networks due to the effects of geomagnetically induced currents (GICs). However, research in this area has been hampered by a lack of GIC observations. Previous studies have noted that New Zealand is unusually fortunate in having a comparatively dense, high quality, set of GIC measurements, spanning >60 transformers in >20 substations. However, due to operational reasons these observations are clustered in the mid and lower South Island. In this paper we analyze space weather‐induced GIC impact patterns over the entire country by using a different set of sensors that monitor levels of harmonic distortion, with even and odd harmonics measured separately. GICs lead to half cycle transformer saturation and is one of the few ways in which even harmonics are produced in a well‐run power transmission network. We make use of harmonic distortion measurements at 377 circuit breakers made at 126 separate locations. Focusing on the intense geomagnetic storm activity during 6–9 September 2017, we show how the even harmonic distortion observations provide a useful new picture of GIC‐stressed transformers. These observations demonstrate how GIC effects can be monitored by using even harmonic distortion in locations where no GIC measurements are present (e.g., the most of the North Island). We understand that harmonic distortion measurements are fairly common in electrical networks and could provide a new tool for space weather researchers.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.
customersupport@researchsolutions.com
10624 S. Eastern Ave., Ste. A-614
Henderson, NV 89052, USA
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
Copyright © 2024 scite LLC. All rights reserved.
Made with 💙 for researchers
Part of the Research Solutions Family.