Abstract-Built upon real-world SCADA and other measurements of a featured utility-scale testbed, this paper addresses the participation of customer side battery energy storage in providing peak load shaving at a 12.47 kV distribution feeder. A stochastic optimization-based battery operation framework is developed that enables feeder load peak shaving under offline (day-ahead) as well as online (close-to-real-time) control settings. Both designs work through establishing a secured communications line to the utility's feeder-level SCADA system. Multiple field experiments are conducted, including a full day test with complete control of a 1 MWh / 200 kW battery system, as well as various numerical assessments based upon one year of real feeder data.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.